HFW - 100 T5

HFW-100 T5
INDUSTRIAL RANGE
Soundproof
Powered by FPT_IVECO
D10
WATER-COOLED
THREE PHASE
50 HZ
STG.2 (FLEXIBLE SCHEME)
DIESEL
HIMOINSA Company
Generating Rates
Power kVA 100 107
Power kW 79 86
Rated Speed r.p.m. 1.500
Standard Voltage V 400
Available Voltages V 230 - 230/132 - 400/230 V
Rated at power factor Cos Phi 0,8
SERVICE PRP STANDBY
HIMOINSA Company with quality certification ISO 9001
HIMOINSA gensets are compliant with EC mark which includes the following directives:
• 2006/42/CE Machinery safety.
• 2006/95/EC Low voltage.
• 2004/108/CE Electromagnetic compatibility.
• 2000/14/EC Sound Power level. Noise emissions outdoor equipment. (amended by 2005/88/EC)
• 97/68/EC Emissions of gaseous and particulate pollutants. (amended by 2002/88/EC & 2004/26/EC)
• EN 12100, EN 13857, EN 60204
Ambient conditions of reference: 1000 mbar, 25ºC, 30% relative humidity. Power according to ISO 3046 normative.
P.R.P. Prime Power - ISO 8528:
Prime power is the maximum power available during a variable power sequence, which may be run for an unlimited
number of hours per year, between stated maintenance intervals. The permissible average power output during a
24 hours period shall not exceed 80% of the prime power. 10% overload available for governing purposes only.
Standby Power (ISO 3046 Fuel Stop power):
Power available for use at variable loads for limited annual time (500h), within the following limits of
maximum operating time: 100% load 25h per year – 90% load 200h per year. No overload available.
Applicable in case of failure of the main in areas of reliable electrical network.